12 Jan 2026
Above ceiling API Gas Pipe alteration Singapore with Full City Energy Gas Submission Compliance
📍The Terrace | 🏨 Condo
A homeowner at The Terrace Condo engaged Homeone to carry out an Above Ceiling API Gas Pipe Alteration as part of their home renovation. The project scope included Gas Pipe Above False Ceiling Alternating, Gas Pipe Sleeving, Regulatory Radiographic Testing and Required step-by-step Submissions, and Commissioning, all in full compliance with Singapore gas regulations. After completing gas-tight sealing performance within the home gas pipe system, we installed the Gas Meter.

Why Compliance Matters for Above Ceiling Gas Pipe Installation
According to applicable standards, only galvanised iron, steel, or copper pipes are permitted for this type of installation, and only steel pipes are allowed to have welded joints.
To meet these requirements, Homeone carried out the Gas Pipe Above False Ceiling Repair using a Steel API Pipe (Grade B) with properly welded joints. All welding works were tested using radiographic inspection in accordance with API 1104, helping to ensure there are no hidden defects and that the installation is safe.
For the gas appliance supply point installation, a transition joint was installed to connect the steel pipe to the copper pipe, ensuring proper material compatibility and a secure gas connection.
In addition, a Syphon Leg was installed at the gas stove appliance point. This method allows condensate (moisture) within the gas pipe to be collected and prevented from entering the appliance, reducing the risk of corrosion, blockage, and performance issues.
Site Assessment & Engineering by LGSW
The project began with a detailed on-site assessment to evaluate the installation conditions, routing requirements, and safety considerations for the above ceiling gas pipe works.
Following this, our Engineering team, led by a Licensed Gas Service Worker (LGSW), developed a technical design and installation plan to ensure full compliance with Singapore standards.

City Energy Gas Submission and Regulatory Approval
Homeone managed the complete City Energy gas submission, including submission of DR01 APPLICATION OF GAS SUPPLY FOR ADDITIONAL AND ALTERATION OF CONSUMER’S INTERNAL PIPE, and the gas pipe design drawings for the above ceiling API Gas Pipe alteration works.
Approval was obtained through CITYGAS FORM GR01, confirming that the proposed installation met all regulatory requirements before installation began.
Gas Pipe Installation, Pressure Testing, and Commissioning
Our LGSW-supervised team carried out the above ceiling API Gas Pipe alteration and gas pipe installation in strict accordance with approved engineering design and safety protocols.
Upon completion, we conducted a Radiographic test and a Final pressure test, and submitted FORM DR04_NOTIFICATION OF FINAL PRESSURE TEST / REQUEST OF TURN-ON OF GAS SUPPLY, followed by successful commissioning and issuance of GR04_STATEMENT OF TURN ON/ COMMISSIONING OF GAS SUPPLY: A & A WORK TO EXISTING INSTALLATION.
- Gas-tightness and leak-free condition
- Proper connection of all components
- Safe operating condition
- Correct gas pressure within operating range
Required Certification and Compliance Documentation
To ensure full LGSW Gas Installation Compliance, Homeone issued the required compliance and commissioning documents, including:
- FORM DR01 & GR1
- FORM DR09 – CERTIFICATE OF CONFORMITY FOR GAS APPLIANCE
- FORM DR04_NOTIFICATION OF FINAL PRESSURE TEST / REQUEST OF TURN-ON OF GAS SUPPLY & GR04_STATEMENT OF TURN ON/ COMMISSIONING OF GAS SUPPLY: A & A WORK TO EXISTING INSTALLATION
- Commissioning report
- FORM DR05 – CERTIFICATE OF FINAL PRESSURE TEST
- FORM DR07 – CERTIFICATE OF PROOF TEST
- FORM DR10 – STATEMENT OF SAFE FOR USE
Safe Operation Briefing and Project Compliance
Upon completion, our team provided a detailed briefing to the homeowner on the safe and proper operation of the gas system, ensuring full understanding of usage and safety practices.
All works, including the above ceiling API Gas Pipe alteration, regulatory submission, installation, testing, and commissioning, were carried out in strict compliance with SS608, Singapore Gas Supply Regulation, and City Energy requirements.
⚠️ Gas Pipe Issue?
For A&A gas works, gas meter installation and above ceiling API Gas Pipe alteration, ensure safe and compliant work.
✔ API 1104 + Radiographic Test
✔ LGSW supervised