Concealed Gas Pipe Repair Service at Tropical Spring
π23 Simei Street 4 | π¨ Condo
A homeowner at Tropical Spring Condominium in Tampines, Singapore contacted Homeone after their Rinnai gas heater failed to ignite properly. Initially, they suspected the water heater itself was faulty. However, the issue turned out to be something much more critical and hidden: concealed gas pipe damage within the wall.
This image shows the puncture in the gas pipe, caused by accidental drilling during previous wall work. Over time, gas leaked into the concealed wall space, preventing the heater from receiving a sufficient gas supply.

Site Findings & Diagnostic Work
Our gas technician confirmed that gas pressure to the heater was insufficient. Using a Bosch D-tect 120 Professional scanner, we traced the concealed pipe and identified the damaged section with minimal hacking.
We shut off the gas supply, vented the system and secured the working area before exposing the concealed pipe for repair.

β Concealed Gas Pipe Repair β Job Scope
(Supervised by EMA-Licensed Gas Service Worker β LGSW)
System Isolation & Safety
- Shut off the gas supply at the meter valve.
- Released trapped gas and confirmed safety with a portable detector.
- Secured and ventilated the work area before opening the wall.
Leak Detection & Exposure
- Traced the concealed copper pipe using a Bosch D-tect 120 Professional scanner.
- Marked and hacked only the affected area to expose the damaged section safely.
Repair Work
- Cleaned the pipe and sealed the puncture using professional brazing technique.
- Brazed joint tested to meet SS 638:2024 and EMA Gas Supply Regulation 21 standards.
Pressure Test & Certification
- Conducted a Final Pressure Test for 5 minutes β no pressure drop observed.
- Issued a Gas Testing Certificate confirming the systemβs safety and compliance.
Finishing & Restoration
- Reinstated the wall with cement patching and final touch-up.
- Cleaned and restored the site before hand-over to the homeowner.


Final Pressure Test & Certification
The repaired gas line was tested under 45 mbar / 450 mm w.g. for a minimum of 5 minutes with zero pressure drop observed.
This testing is performed in compliance with SS 638:2024 and the EMA Gas Supply Regulation 21 to ensure the gas installation remains safe for continued operation.
A Gas Testing Certificate was issued to the homeowner as verification that the concealed gas pipe is secure and compliant with national gas safety requirements.
Safe Completion & Customer Assurance
Once the concealed gas leak was properly sealed and pressure-tested, the Rinnai gas heater regained full and reliable ignition. The entire gas installation is now certified safe for continued operation.
For any concealed gas pipe damage, gas smell or heater malfunction, Homeone Gas Services is ready with licensed and compliant gas pipe repair across Singapore, ensuring peace of mind and safety for your home.
Speak With Our Gas Specialist Now
We are here to help with gas system issues and gas pipe repairs.
Available daily for urgent assistance.
All gas works are supervised by licensed and trained professionals.